BSW Contractors Ltd carry out a Post Construction Clean which undertakes the cleaning of various types of computer rooms / data rooms / server rooms / CER rooms based on ISO 14644-1 2015 to Class 8.
Once cleaned, we validate the room using an independent company to test the quality of air and to certificate the room to show the level and size of particulates present within the room.
ISO 14644-1 Class 8 or better plus all accessible surfaces to be free from dust.
This specification is based on ISO 14644-1 2015 which is a clean room and controlled environment specification.
There are 9 Classes, of which Class 8 is the most commonly specified. Class 8 limits the particulate levels for the three size of particulate: 0.5 micron 1 micron and 5 micron. The number of particles allowed per cubic metre are 3,520,000; 832,000 and 29,3000 respectively.
After the validation is complete we will carry out a full survey based on ISO 14644-1 2015 to Class 8 or better. We will then produce a report and certificate to show the room conforms to this specification.
Particle Size |
||||||
Class |
0.1 µm |
0.2 µm |
0.3 µm |
0.5 µm |
1 µm |
5 µm |
ISO 1 |
10 |
2 |
|
|
|
|
ISO 2 |
100 |
24 |
10 |
4 |
|
|
ISO 3 |
1,000 |
237 |
102 |
35 |
8 |
|
ISO 4 |
10,000 |
2,370 |
1,020 |
352 |
83 |
|
ISO 5 |
100,000 |
23,700 |
10,200 |
3,520 |
832 |
29 |
ISO 6 |
1,000,000 |
237,000 |
102,000 |
35,200 |
8,320 |
293 |
ISO 7 |
|
|
|
352,000 |
83,200 |
2,930 |
ISO 8 |
|
|
|
3,520,000 |
832,000 |
29,300 |
ISO 9 |
|
|
|
35,200,000 |
8,320,000 |
293,000 |